Technical Data:
Dimension (mm):
Parameters(25°C)Model
SCY10-
800A
1000A
1200A
1500A
2000A
2500A
3000A
Nominal Rms Current (Ipn)
±800AT
±1000AT
±1200AT
±1500AT
±2000AT
±2500AT
±3000A
Measuring Range (Ip)
2*Ipn
Load resistance Rmax
≥10kΩ
Output Voltage
±4V
Working voltage
DC ±12V or ±15V(±5%)
Accuracy @ Ta=25°C
±1%
Linearity @ Ta=25°C
±1%
Withstand voltage
3kVrms/50Hz/min
Offset Voltage
< ±30mV
Offset temperature characteristics
< ±0.1%/°C
Thermal drift of Vo
< ±1mV/°C (If=0)
Hysteresis offset
< ±25mV (if=F.S.)
Response time
< 7uS
Bandwidth (-3db)
± DC - 4KHZ
Current consumption
<±23mA
Operating temperature
-40~+85 °C
Storage temperature
-40~+85 °C
Instrucations
SCY10 Series Split Core Hall Effect Current Sensor is dual power supply hall current sensor, open loop measurement.
There is galvanic isolation between primary and secondary circuit of the sensor, it can measure DC, AC or pulse currents.
SCY10 Series 's up and down can open and close without removing the busbar line, easy to install.
Big square hole perforation, mainly measure cooper conductor current.
Features: High accuracy, low power consumption, high liability and strong overload capacity.