必赢437app登录入口-首页欢迎您

CN EN

SCK18 Series Hall-Effect Current Sensor

SCK18 Series Hall Open Loop Current Sensor is a new generation open loop current sensor based on Hall effect principle, it can accurately measure DC, AC and pulse current and other various irregular waveforms current in electrical isolation condition

Back Download

General Data:

Parameters(25°C) Model SCK18-
300A 400A 500A 600A 800A 1000A 1200A 1500A 2000A
Nominal Rms Current (Ipn) ±300AT ±400AT ±500AT ±600AT ±800AT ±1000AT ±1200AT ±1500AT ±2000AT
Measuring Range (Ip) 2*Ipn
Load resistance Rmax ≥10kΩ
Output Voltage ±4V
Working voltage DC  ±12V~±15V(±5%)
Accuracy @ Ta=25°C ±1% FS
Linearity @ Ta=25°C ±1% FS
Withstand voltage 3kVrms/50Hz/min
Offset Voltage < ±30mV
Offset temperature characteristics < ±0.1%/°C
Thermal drift of Vo < ±1mV/°C (If=0)
Response time < 5uS
Hysteresis offset < ±25mV (if=F.S. 0 <---> Nominal RMS Current)
Current consumption <±15mA
Operating temperature -20~+80 °C
Storage temperature -40~+85 °C
Dimension(mm):

Notes:

1. Size error: ±1mm;
2. Primary aperture: □40*30mm;
3. Fastening hole: φ4.5mm*2;
4. The output terminal is compatible with Molex 5045-04A;
5. The IP indication direction is the positive direction of the current;
6. The temperature of the primary conductor shall not exceed 105°C;
7. Incorrect wiring may cause damage to the sensor.


Instructions
1. SCK18 Series is open-loop current sensor. There is galvanic isolation between primary and secondary circuit of the sensor, it can measure DC, AC or pulse currents.
2. Big square perforation, mainly measure cooper conductor current.
3. Features: High accuracy, low power consumption, high liability and strong overload capacity.

Shenzhen Socan Technologies Co.,Ltd

Top003101-logo1.png

Address:4th Floor, A3 Bld, Xin Jian Xing Industrial Park, Feng Xing Rd, Guangming Street, Guangming New District, Shenzhen, China

Tel:86-0755-33263060

Fax:+86-0755-33263006

E-mail:sales@szsocan.com

Quote

Name:
Phone:
E-mail:
Content: